Hydran* M2-X Instruction Manual
Page 146
MA-029 Rev. 1.0, 30-Jul-18
*Hydran M2-X H2 accuracy is specified up to 2000ppm; at concentrations
above 2000ppm the device continues to provide trending to 5000ppm, but
potentially outside the published accuracy specification.
This is because the Hydran M2-X H2 calibration and performance is
optimised and tested in the factory in the key range of concentrations for
Transformer diagnostics. At values >2000 ppm, the H2 level has exceeded
IEEE Condition 4 (Major event at > 1800ppm), hence customer action
should have already occurred within the specified measurement range for
the M2-X.
External
Sampling Port
Designed for glass syringe with Luer stop cock; closed with
5/32-in (approximately 4 mm) Allen screw
ELECTRONIC UNIT
Hardware
Microprocessor; watchdog; clock with battery backup
Software
Real-time operating system; menu-driven interface
Functions
Gas level, hourly trend and daily trend readings
Gas level and gas trends alarms
Moisture level and moisture average alarms
Alarms due to system fault conditions
History data logging (Short Term, Long Term, Events and
Service)
Periodic sensor test
Calibration, configuration and self-test
Networking
Remote embedded software upgrading
Display
Backlit liquid crystal display (LCD); graphic 128 x 64 pixels
Keypad
Keypad 8 keys: Up, Down, Left, Right, Esc and 3 context
functions Alarm Contacts
Alarm Contacts
4 SPDT alarm relays (Type C) which can be configured for:
Gas (level and trend) and analog High contacts
Gas (level and trend) and analog High-High contacts
Moisture (level and average) and analog High contacts
Moisture (level and average) and analog High-High contacts
Relay contact maximum switching capacity:
Resistive load: 50 VA, 60 W (power factor = 1)
Inductive load: 25 VA, 30 W (power factor = 0.4, L/R = 7 ms)
Relay contact maximum operating current:
Resistive load: 3 A (ac/dc)

Table of Contents

Other manuals for GE Hydran M2-X

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Hydran M2-X and is the answer not in the manual?

GE Hydran M2-X Specifications

General IconGeneral
BrandGE
ModelHydran M2-X
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals