Hydran* M2-X Instruction Manual
Page 156
MA-029 Rev. 1.0, 30-Jul-18
4.3.8
Grounding the Hydran M2-X Enclosure
86
1. Connect a ground wire to the Hydran M2-X’s external ground lug
[ ]
2. Ground the other end of this cable to the transformer ground grid
[ ]
4.3.9
Installing the Cable Conduits
87
1. Remove the cover’s four retaining screws
[ ]
2. Pull the cover
[ ]
3. Install the necessary watertight conduit fittings
[ ]
4. Mount a conduit to each conduit fitting
[ ]
5. Ground the conduits and/or cable shields at some point
[ ]
4.3.10
Installing the Cables
89
4.3.10.
2
Alarm Cable (if Used)
90
1. Run the cable through a conduit
[ ]
2. Verify all wires are identified at both ends
[ ]
3. Connect the wires to the alarm contacts terminal block
[ ]
4. Connect the other end of the cable to the SCADA system
[ ]
4.3.10.
3
Standard TDM Signal (Optional)
90
1. Run the cable through a conduit
[ ]
2. Verify all wires are identified at both ends
[ ]
3. Connect the wires to the TDM/RS-485 terminal block
[ ]
4. Connect the other end of the cable to the Hydran 201Ci-1 or Hydran 201Ci-4
Controller
[ ]
4.3.10.
4
Analog Input Cable (if Used)
90
1. Run the cable through a conduit
[ ]
2. Verify all wires are identified at both ends
[ ]
3. Connect the wires to the corresponding I/O terminal block
[ ]
4. Connect the other end of the cable to the sensor
[ ]

Table of Contents

Other manuals for GE Hydran M2-X

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Hydran M2-X and is the answer not in the manual?

GE Hydran M2-X Specifications

General IconGeneral
BrandGE
ModelHydran M2-X
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals