Hydran* M2-X Instruction Manual
MA-029 Rev. 1.0, 30-Jul-18
4.3.10.
5
Analog Output Cable (If Used)
91
1. Run the cable through a conduit
[ ]
2. Verify all wires are identified at both ends
[ ]
3. Connect the wires to the corresponding I/O terminal block
[ ]
4. Connect the other end of the cable to the SCADA system
[ ]
4.3.10.
6
AC Power Supply Cable
91
1. Run the cable through a conduit
[ ]
2. Remove the plastic cover from the ac power supply terminal block
[ ]
3. Connect the wires to the ac power supply terminal block
[ ]
4. Connect the other end of the cable to the power source
[ ]
4.3.11
Verifying the Hydran M2-X Operation
92
1. Fasten the cover with the four screws
[ ]
2. Verify all cable entry points to ensure they are watertight
[ ]
3. Verify the heating plate is warm
[ ]
4.4
Configuring the Hydran M2-X
92
4.4.1
Setting the Date and Time
92
1. Set Current Date
[ ]
2. Set Current Time
[ ]
4.4.2
Setting the Parameters of the History Files
93
1. Set Short Term Rate to _________ minutes
[ ]
2. Set Long Term #1 to _________
[ ]
3. Set Long Term #2 to _________
[ ]
4. Set Long Term #3 to _________
[ ]
5. Set Long Term #4 to _________
[ ]
6. Erase the content of Short Term history file
[ ]
7. Erase the content of Long Term history file
[ ]
4.4.3
Setting the Alarm Parameters
93
1. Wait 30 minutes or until levels are stable
[ ]