Description Test Standard Group Test Level
IEC 61000-6-4:2011
IEC 60255-26:2013
Com, RJ45 ports
0,15 MHz to 0,5 MHz:
97 dB( μ
-peak
84 dB( μ
53 dB( μA) to 43 dB( μA) quasi-peak
40 dB( μA) t o 30 dB(μA) ave
0,5 MHz to 30 MHz:
87 dB( μV) quasi-peak
74 dB( μV) average
43 dB( μA) quasi-peak
30 dB( μA) average
Radiated Emissions
IEC 61000-6-4:2011
IEC 60255-26:2013
Enclosure port
30 - 230MHz:
40dB( μV/m) quasi-pe
ak at 10m and 3m measuring
distances.
230 - 1000MHz:
47dB( μV/m) quasi-
peak at 10m and 3m measuring
distances.
1 GHz to 3 GHz:
56dB( μ
76dB( μ
3 GHz to 6 GHz:
60dB( μV/m) average at 3m easuring distance.
80dB( μ
10.3.2.7 Immunity
Description Test Standard Mode Group Test Level
Conduced disturbances,
induced by radiofrequency
fields
IEC 61000-4-6:2013
IEC 60255-26:2013
DC and AC Power
ports, earth port,
signal ports
Level 3 : 10V (rms)
Disturbance signal 80% AM
with a 1KHz sine wave, 150Ω
Frequency sweep from 150kHz
to 80MHz
Spot frequencies: 27 MHz
±0,5% & 68 MHz ±0,5%
Radiated, radio-frequency
electromagnetic field
IEC 61000-4-3:2010
IEC 60255-26:2013
6 Faces Enclosure ports
Level 3 : 10V/m (rms)
Frequency sweep:
from 80MHz to 3000MHz
Spot frequencies:
80 MHz ± 0,5 %
160 MHz ± 0,5 %
380 MHz± 0,5 %
450 MHz ± 0,5 %
900 ± 5 MHz
1 850 ± 5 MHz
2 150 ± 5 MHz