EasyManua.ls Logo

GE Reason H49 - Page 121

GE Reason H49
158 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GE Reason H49
Technical Manual
H49/EN M/C22
121
Description Test Standard Mode Group Test Level
IEC 61000-4-3:2010 6 Faces Enclosure ports
Level 4 : 30V/m (rms)
Frequency sweep:
from 800MHz to 960MHz
from 1400MHz to 2000MHz
Electrostatic Discharge
IEC 61000-4-2:2008
IEC 60255-26:2013
Enclosure ports
Level 4:
15kV air discharge.
8kV contact discharge.
Surge Immunity
IEC 61000-4-5:2014
IEC 60255-26:2013
DM
AC/DC Power, Alarm,
binary Input/Output
Ports
Level 3:
Source impedance 2Ω, Line-to-
line 2kV,
coupling resistor 0Ω, coupling
capacitance 18 µF
CM
Level 4:
Source impedance 2Ω, Line-to-
earth 4kV,
coupling resistor 10Ω, coupling
capacitance 9 µF
DM Signal ports
Level 4:
Source impedance 2Ω, Line-to-
ground 4kV,
coupling resistor 40Ω, coupling
capacitance 0,5 µF
Power frequency magnetic
field
IEC 61000-4-8:2009
IEC 60255-26:2013
Enclosure port
Level 5:
100A/m continuous (≥60s)
1000A/m for 1s
Pulsed magnetic field
immunity
IEC 61000-4-9:2001
Enclosure port
Level 5:
1000A/m peak
Applied 6.4/16µs magnetic field
pulses in all planes for the EUT
in a quiescent state.
Damped oscillatory
magnetic field immunity
IEC 61000-4-10:2001 - 11
Enclosure port
Level 5:
100A/m peak
Applied in all planes at:
100kHz, repetition rate ≥ 40Hz,
during 60s
1MHz, repetition rate ≥ 400Hz,
during 60s
Slow damped oscillatory
wave
IEC 61000-4-18:2011
IEC 60255-26:2013
CM
DC and AC Power
Level 3:
2.5kV @100kHz and 1MHz
DM
DC and AC Power
Level 3:
1kV peak voltage @100
kHz and
1MHz
CM
Ethernet ports
Level 3:
2.5kV @100kHz and 1MHz

Table of Contents