July 2010 23 – 393
With the table for the PLC inputs you can check the condition of the MB keys (pressed or
not):
8 Switch on the machine.
8 Press the EMERGENCY STOP button.
8 Call the table with the PLC inputs. --> See “The TABLE function” on page 11 – 119.
8 Press the keys. --> The respective inputs must change to 1!
Exception: I147 = NC STOP, changes to 0 when actuated (broken wire interlock!)
Figure: Observation of the NC-START button in the PLC table
Note
You can measure the voltage of the inputs, e.g., with a connected test adapter.
The logic state in the PLC-TABLE must be in agreement with the voltage level of each input!