10 – 100 HEIDENHAIN Service Manual iTNC 530
10.2 Activation and Settings
8 Select the Programming and Editing operating mode.
8 If open: Close the program management by pressing the END button.
8 Press the MOD key.
8 Press the DIAGNOSIS soft key.
8 Press the DRIVE DIAGNOSIS soft key.
8 Press the OSCI soft key. --> The setup menu appears.
8 Use the arrow keys to position the cursor to the respective input fields.
8 Press the GOTO key to open one of the selection windows.
Pressing the MOD key while the program manager is open calls the interface settings.
The integrated oscilloscope can also be called by entering the code number 688379.