July 2010 4 – 47
Ext. In-/output not
ready
The interface is not connected.
The external device is not switched on or is
not ready.
The transmission cable is defective or
incorrect.
Check the data transmission line.
See “Connection Setup” on page 13 – 172.
External
EMERGENCY
STOP
The "control-is-ready" PLC input is not active. Release the EMERGENCY STOP switch
Retract axis
Check the EMERGENCY STOP chain (See
“Checking the "Control is ready" output and
input (EMERGENCY STOP chain)” on page
16 – 233).
If "Control is ready“ output is defective -->
Replace MC 320 (See “Exchange of the MC
422 B, MC 422 C, MC 420” on page 28 –
542).
EMERGENCY STOP key pressed on
machine operating panel or handwheel
Axis is on hardware limit switch
Wiring interrupted
Relays, safety contactor combinations
defective
X34 is not powered with 24 V
"Control is ready" output of MC 320
defective.
Release the EMERGENCY STOP switch
Retract axis
Check the EMERGENCY STOP chain (See
“Checking the "Control is ready" output and
input (EMERGENCY STOP chain)” on page
16 – 233).
If "Control is ready“ output is defective -->
Replace MC (See “Exchange of
HEIDENHAIN Components” on page 28 –
523).
See “Checking the Enables on the iTNC
530” on page 16 – 229
Incorrect
reference position
<axis>
Signal of the reference pulse is disturbed
(ground shield).
Position determination via Z1-track is
defective.
Wrong encoder line count.
Take measures for noise suppression.
Check the motor table.
Inform your service agency.
See “Speed Encoders” on page 18 – 293.
Error: Profibus
configuration
An error occurred during evaluation of the
Profibus configuration.
Inform your service agency.
Synchronization
monitoring <axis>
The positions of two synchronized axes
differ by a value greater than that defined in
machine parameter MP855.
Reduce the feed rate and increase the
spindle speed.
Remove potential sources of vibration.
If this occurs frequently: Inform your service
agency.
Handwheel? Electronic
handwheel not connected
Incorrect handwheel selected in machine
parameter MP 7640
The transmission line is defective or
incorrect.
Connect the handwheel via cable adapter.
Check machine parameter MP 7640.
Inspect the data transfer line for damage.
See “Handwheel” on page 24 – 399.
Error message Possible cause of error Measures for error diagnosis and/or
corrective action
Additional information and descriptions in
the manual
Additional information and descriptions in
the manual