July 2010 3 – 679
Motor overload with I
2
t monitoring
Machine
parameters
MP2302.x Factor for I
2
t monitoring of motor
Input: 0 to 1 000.000 [· rated current of motor or standstill current]
0: I
2
t monitoring of motor switched off
1: Rated current of motor or standstill current is reference value
MP2304.x Factor for I
2
t monitoring of the power module
Input: 0 to 1000.000 [· rated current of power module]
0: I
2
t monitoring of power module switched off
1: Rated current of power module is reference value
Interrogation
through
PLC module
Module 9160 Status request from temperature monitoring and I
2
t-monitoring.
The I
2
t monitoring reported by the module is given with respect to the first I
2
t monitor response
(power stage or motor), if both I
2
t monitors are activated (MP2302.x, MP2304.x). This early
warning is withdrawn as soon as the limit for reset is reached.
Call:
CM 9160
PL D <>Temperature monitoring>
Bit 15876543210
Axis:Sxxxxx987654321
PL D <> I2t monitoring I2t early warning>
Bit 15876543210 15 876543210
Axis Sxxxxx987654321 Sxxxxx987654321
Error recognition:
Temperature
models
The temperature model of the motor or power module is defined by the entries in the motor
table or power module table, respectively (motor.mot, inverter.inv). Remember that calculation
of which temperature model to use depends exclusively on the availability or nonavailability of
the parameters. In addition, the parameters for motors and power modules are to be evaluated
separately.
Markers Value Meaning
M4203 0 No error
1 Control has no current controller