Troubleshooting
Service Manual
190
Troubleshooting procedure
SMGB0066 rev.0 - 12/2009
 
1

• ThealarmcodeisdisplayedonthePCB´sdisplay.
This alarm code is displayed when the water outlet temperature thermistor is short circuited or cut.

Are the connectors between
PCB1 and PCB2 correctly
connected?
PCB1
CN9-CN1
PCB2
CN5-CN2
CN6-CN3
CN2-CN4
No
Yes
Pull out connector
and measure thermistor
resistance.
Isresistancecorrect?
No
Replace thermistor
Yes
Is connector CN13 on
PCB2correctlyconnected?
No
Yes
Wiringcheck,Repair.
(Breakingofwire,wrongwiring)
Wiringcheck,Repair.
(Breakingofwire,wrongwiring)
Check PCB1 and PCB2


Temperature (ºC)
Thermistor
Resistance (kΩ)
note
Measure the resistance at least in 2 different points which the temperature is different more than 10 ºC. -