191
Troubleshooting procedure
SMGB0066 rev.0 - 12/2009
Troubleshooting
Service Manual
7
 
1

• ThealarmcodeisdisplayedonthePCB´sdisplay.
This alarm code is displayed when the chilled water temperature is lower than 2ºC.

Is connector CN9 on the
PCB2correctlyconnected?
Wiring Check
(Breakingofwire,wrong
wiring)
No
Yes
Is the actual water
temperature and the
temperature shown in
segmentproper?
Yes
No
Check pump reverse rotation
Check water strainer clogging
Check air mixing
Are the connectors
between PCB1 and PCB2
correctlyconnected?
PCB1
CN9-CN1
PCB2
CN5-CN2
CN6-CN3
CN2-CN4
No
Wiringcheck,Repair.
(Breakingofwire,wrong
wiring)
Yes
Pull out connector
and measure thermistor
resistance.
Isresistancecorrect?
No
Replace thermistor
Yes
Check PCB1 and PCB2
Checkthewaterowrate
(Check temperature of Inlet)
Check 4-way valve