Troubleshooting
Service Manual
198
Troubleshooting procedure
SMGB0066 rev.0 - 12/2009
• ThealarmcodeisdisplayedonthePCB´sdisplay.
– This alarm code is displayed when the thermistor is short circuited or cut.
Are the connectors
between PCB1 and PCB2
correctlyconnected?
PCB1
CN9-CN1
PCB2
CN5-CN2
CN6-CN3
CN2-CN4
No
Yes
Pull out connector
and measure thermistor
resistance.
Isresistancecorrect?
No
Replace thermistor
Yes
Is connector CN11 on
PCB2correctlyconnected?
No
Yes
Wiringcheck,Repair.
(Breakingofwire,wrongwiring)
Wiringcheck,Repair.
(Breakingofwire,wrongwiring)
Check PCB1 and PCB2
Temperature (ºC)
Thermistor
Resistance (kΩ)
note
Measure the resistance at least in 2 different points which the temperature is different more than 10 ºC. -