199
Troubleshooting procedure
SMGB0066 rev.0 - 12/2009
Troubleshooting
Service Manual
7
• ThealarmcodeisdisplayedonthePCB´sdisplay.
– This alarm code is displayed when the high pressure sensor is short circuited or cut.
Is the high pressure sensor
correctly connected to
connectorCN4onPCB1?
No
Yes
Yes
No
Is high pressure sensor
output character and low
pressure sensor display value
"Ps" proper during compressor
stop?.(Seetableabout
sensor characteristics)
Is the voltage between
VCC05T and GND1 on
PCB15V?
(Refer to voltage test position)
Yes
No
Failure of power supply circuit
on PCB1. Replace PCB1.
Wiringcheck,Repair.
(Breakingofwire,wrongwiring)
Failure of high pressure sensor.
Replace high pressure sensor.
Failure of component on PCB1.
Replace PCB1.
Pressure (MPa)
Output
(PCB1)
High Pressure Sensor
(0~5V) Voltage meter
Red
(+Power
Supply)
White (Out)
Black (Gnd)
note
In case that the low pressure is higher than 2.2 MPa, segment shows 2.2 MPa. -
In this case, connect a pressure gauge to high pressure check joint, check the pressure shown in the gauge. -