Troubleshooting
Service Manual
200
Troubleshooting procedure
SMGB0066 rev.0 - 12/2009
8
• ThealarmcodeisdisplayedonthePCB´sdisplay.
– This alarm code is displayed when the low pressure sensor is short circuited or cut.
Is the high pressure sensor
correctly connected to
connectorCN4onthePCB1?
No
Yes
Yes
No
Is low pressure sensor
output character and high
pressure sensor display value
"Pd" proper during compressor
stop?.(Seetableabout
sensor characteristics)
Is the voltage between
VCC05T and GND1 on
PCB15V?
(Refer to voltage test position)
Yes
No
Failure of power supply circuit
on PCB1. Replace PCB1.
Wiringcheck,Repair.
(Breakingofwire,wrongwiring)
Failure of low pressure sensor.
Replace low pressure sensor.
Failure of component on PCB1.
Replace PCB1.
Is the low pressure sensor
correctly connected to
connectorCN3onthePCB1?
No
Yes
Wiringcheck,Repair.
(Breakingofwire,wrongwiring)
Pressure (MPa)
Output
(PCB1)
Low Pressure Sensor
(0~5V) Voltage meter
Red
(+Power
Supply)
White (Out)
Black (Gnd)