132
On lines that pass, the pressure builds up from 0-3 psig to 10-15 psig. On lines that fail,
you will see little or no pressure build-up.
10.5.3.6.
Configuration problems
You may still run into problems. The Line Leak Test has configurable variables: the
pass/fail set point (typically 7-10 psig) and the test time per point. If some tubing runs are
unusually long, more test time may be needed. Honeywell can change the configuration if
necessary.