144
Ref.
Function
Code
Register Channel
Type Function Value Remark
48160 - Unsigned short
The latest scanned point# (4th point)
101-160
(value = 100 + point#)
Composite
scan only
48161-48176 - Unsigned short
The gas concentration of the latest scanned
point# (4th point)
0-65535
Composite
scan only
48200 - Unsigned short
Heartbeat 0-65535
48201 - Unsigned short
Major Malfunction
(Service event level: System down)
0-100
48202 - Unsigned short
Minor Malfunction
(Service event level: Required service)
0-100
48203 - Unsigned short
CCITT CRC16 Checksum Single Scan (A) 0x0000 ~ 0xFFFF
48204 - Unsigned short
CCITT CRC16 Checksum Composite Scan B 0x0000 ~ 0xFFFF
48205 - Unsigned short
CCITT CRC16 Checksum Composite Scan C 0x0000 ~ 0xFFFF
48206 - Unsigned short
CCITT CRC16 Checksum Composite Scan D 0x0000 ~ 0xFFFF
48207 - Unsigned short
Information (Service event level: Information) 0-100
New for
ACM150 G2
48208 - Unsigned short
Simulation mode on/off status
0x0000: Board simul OFF, Bench simul OFF
0x0001: Board simul OFF, Bench simul ON
0x0002: Board simul ON, Bench simul OFF
0x0003: Board simul ON, Bench simul ON
0-3
New for
ACM150 G2
48301-48316 NA
ASCII
(Char * 32)
Software version
ex.0.4.1 (0x302E 342E 3100… 0000.)
-
New for
ACM150 G2
48317 NA Unsigned short
High byte: Operation mode
0x01xx: Automatic mode
0x02xx: Test mode (Manual mode/ Panel
mode)
Low byte: Request type
0xXX01: normal scan
0xXX02: composite scan
0xXX03: background scan
0xXX04: factory background scan
0xXX05: demand scan
0xXX06: lock on scan
0xXX07: kinked tube test
0xXX08: line leak test
-
New for
ACM150 G2