4. OPERATION
Congure4-20mA Conguration Menu
Providesthemeanstocongurethevaluesforthe4-20mAsignaloutputsettings.Threesettingsare
available:
Inhibit Value 1mA to 4mA, default is 1mA.
Warning Value 1mA to 6mA, default is 3mA.
Overrange Value20mAto21.5mA,defaultis21mA.
Caution:WhencompliancewiththeATEXperformancestandardisrequiredthewarningandinhibit
currentshallnotbeconguredtoavaluebetweenthan3.1mAand4.9mA
Onceconguredtoanewvalue,thenewvalueisoutputwhenthecorrespondingstatesoccur.
WhentheWarningcurrentisconguredtobegreaterthan4mAtheoutputpulsestothecongured
Warningcurrentforapproximately1secondevery10seconds.
Change Cartridge
ok
Change
cartridge
Change Cartridge screen
Checking
Success?
Yes
No
ok
ok
Fault diagnosis
Calibration Menu
Follow cartridge
change
instructions
See Section 5