EasyManuals Logo

Honeywell EXCEL 5000 User Manual

Honeywell EXCEL 5000
282 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #151 background imageLoading...
Page #151 background image
EXCEL CARE CONTROL ICONS ALPHABETIC REFERENCE
153 74-5577–33 (US)
EN2B-0184 GE51 R0518 (Europe)
Excel Web / Excel Web II
Minimum pre-heat time
(with room sensor) P4 Number type: Whole number, Unit: Minutes
Default: 120 min, Range: 0 through 1440 min
Maximum pre-heat time
(only Excel Web / Excel Web II) Number type: Whole number, Unit: Minutes
Default: 2880 min, Range: > 0
Maximum pre-heat setpoint
(with room sensor) P8 Number type: Decimal, Unit: Degrees Fahrenheit
Default: 175F (80C), Range: 32 through 302F (0 through 150C)
No room sensor
constant P6 Number type: Decimal, Unit: F Deg
Default: 20 F Deg (10K), Range: 0 through 36 F Deg (0 through 20K)
Optimum stop outdoor air
temperature low limit P7 Number type: Decimal, Unit: Degrees Fahrenheit
Default: 32F (0C), Range: 14 through 59F (-10 through +15C)
Pre-heat time at 0C
outdoor air temperature
(with room sensor) Number type: Whole number, Unit: Minutes
Default: 120 min, Range: 0 through 1440 min
Optimum stop (with
room sensor) P9 Number type: Whole number, Unit: Minutes/F Deg
Default: 20min/F Deg, Range: 0 through 110 min/F Deg

Table of Contents

Other manuals for Honeywell EXCEL 5000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell EXCEL 5000 and is the answer not in the manual?

Honeywell EXCEL 5000 Specifications

General IconGeneral
BrandHoneywell
ModelEXCEL 5000
CategoryControl Systems
LanguageEnglish

Related product manuals