EasyManua.ls Logo

Honeywell EXCEL 5000

Honeywell EXCEL 5000
282 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ALPHABETIC REFERENCE EXCEL CARE CONTROL ICONS
74-5577–33 (US) 44
EN2B-0184 GE51 R0518 (Europe)
Decimal Places (Excel Web / Excel Web II)
Function Returns the value of the decimal places part of the input value (X=3.175 becomes
Y=0.175)
I/O Dialog Box
Input One analog input (X).
Output One analog output (Y).
Internal Parameters None.
Delay (Excel Web / Excel Web II)
Function “Switch-on” delay.
I/O Dialog Box
Inputs Two digital inputs (A and B)
Outputs Two digital outputs where:
Y will become value of A after delay time:
If A < 1, then Y = 0
If A >= 1, then Y = 1 (after delay time)
If A < 1 within delay time, delay time is reset
Alarm indicates a difference between the two inputs:
If Y = 1 and input B < 1, then alarm signal = TRUE (1),
Internal Parameter
Parameter Description
P1 Delay time with 10 sec value and a limit of 0<=x.

Table of Contents

Other manuals for Honeywell EXCEL 5000

Related product manuals