EasyManua.ls Logo

Honeywell EXCEL 5000

Honeywell EXCEL 5000
282 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EXCEL CARE CONTROL ICONS ALPHABETIC REFERENCE
23 74-5577–33 (US)
EN2B-0184 GE51 R0518 (Europe)
Internal Parameters None.
Example See the Examples chapter for a description of how to use the ADD icon in a floating
limits and alarm suppression application.
Also see the Data Transfer (IDT) section for examples that show how to use ADD
with IDT.
ADH2 (Excel Web / Excel Web II)
Function Legacy RACL function: Calculates the slope S of the heating curve for the
determination of the flow temperature setpoint option to adapt the slope to the
building characteristics.
I/O Dialog Box
Inputs Five inputs where:
TSet = room temperature setpoint
TRm = room temperature
TOat = outside air temperature (req. with adaptation)
TWtr = supply water temperature (req. with adaptation)
SPmp = heating pump status (req. with adaptation)
Outputs Two outputs where:
Valid = slope value validity (0=invalid, 1=valid)
Valid means the slope value is in a possible relation to the inputs, e.g. values below
the freezing point may be impossible.
Slope = calculated slope value
Internal Parameters
Parameter Description P1 Adaptation (0 = no adaptation, 1 = adaptation) with default = 0 and a limit
of 0 < = x < = 1.
P2 Heating curve slope with default = 1, 6 and a limit of 0 < = x < = 4.
P3 Heating curve curvature with default = 1,33 and a limit of 0 < = x < = 2.

Table of Contents

Other manuals for Honeywell EXCEL 5000

Related product manuals