ALPHABETIC REFERENCE EXCEL CARE CONTROL ICONS
74-5577–33 (US) 228
EN2B-0184 GE51 R0518 (Europe)
Time Counter (Excel Web / Excel Web II)
Function Counts the runtime when the input signal X is greater than or equal to 1. If the
counter reset signal Rst
is greater than or equal to 1, the runtime is reset to 0.
I/O Dialog Box
Inputs Two inputs where:
X = input signal (>= 1 start counting runtime)
Rst = reset signal (>= 1 reset runtime to 0)
Outputs Two outputs where:
Hr on = runtime in hours
Min on = runtime in minutes
Internal Parameters None.
Timer Value (Excel Web / Excel Web II)
Function Legacy RACL function "RTIM": Counts the time in seconds. Can be reset by the
"Reset Timer" function.
I/O Dialog Box
Outputs One analog output (T). Timer value in sec.
Internal Parameters None.
Truncate (Excel Web / Excel Web II)
Function Truncates the decimal places, e.g. 3.1 becomes 3, -3.1 becomes -3)
I/O Dialog Box
Input One analog input (X).
Output One analog output (Y).
Internal Parameters None.