ALPHABETIC REFERENCE EXCEL CARE CONTROL ICONS
74-5577–33 (US) 168
EN2B-0184 GE51 R0518 (Europe)
Dead time short P8 Number type: Whole number, Unit: Minutes
Default: 5 min, Range: 0 through 60 min
Time constant short P9 Number type: Whole number, Unit: Minutes,
Default: 75 min, Range: 0 through 2880 min
Dead time long P10 Number type: Whole number, Unit: Minutes
Default: 5 min, Range: 0 through 60 min
Time constant long P11 Number type: Whole number, Unit: Minutes
Default: 150 min, Range: 0 through 2880 min
Building model adaption P12 Number type: Whole number, Unit: None
Default: 1, Range: 0 through 2, (0 = disabled; 1 = enabled, 2 = restart)
Room control P-band P13 Number type: Decimal, Unit: %/K
Default: 10.0 K; Range: >=0
Integral action time P14 Number type: Decimal, Unit: Seconds
Default: 300.0 s, Range: >= 0
Maximum flow
temperature P15 Number type: Decimal, Unit: Degrees Celsius
Default: 80.0 °C, Range: 0 through 150.0 °C
Heating curve curvature P16 Number type: Decimal, Unit: none
Default: 1.33, Range: 0 through 2.0
Heating curve slope P17 Number type: Decimal, Unit: none
Default: 1.6, Range: 0 through 4.5
Max. heating curve slope
for adaptation (with room sensor) P18 Number type: Decimal, Unit: none
Default: 4.5, Range: 0.4 through 4,5
Heating curve
adaptation mode P19 Number type: Decimal, Unit: none
Default: 2, Range: 0 through 4; (0 = disabled; 1 = enabled, 2 = restart; 3 =
adaptation refreshed new start; 4 = direct RMT compensation
Occupied/ unoccupied
changeover P20 Number type: Decimal, Unit: Degree Celsius
Default: 16 °C, Range: 0 through 30 °C
Frost protection
limit P21 Number type: Decimal, Unit: Degree Celsius
Default: 2 °C, Range: 0 through 15 °C
Boost factor
P22 Number type: Decimal, Unit: none
Default: 1, Range: 0 through 30
Room temperature
multiplier P23 Number type: Decimal, Unit: Degree Celsius
Default: 4 °C, Range: 0 through 50
Minimum room
temperature P24 Number type: Decimal, Unit: Degree Celsius
Default: 13 °C, Range: 0 through 30 °C
Differential minimum room
temperature P25 Number type: Decimal, Unit: Kelvin
Default: 2 K, Range: 0 through 10 K
Parameter Number
Descriptions P1 Minimum preheat time
P2 Maximum preheat time
P3 No room sensor compensation