ALPHABETIC REFERENCE EXCEL CARE CONTROL ICONS
74-5577–33 (US) 240
EN2B-0184 GE51 R0518 (Europe)
Comfort range P3 Number type: decimal, Unit: Deg
Default: 4.0 Deg, Range: 0 through 30
This value defines the width of the heating, cooling, and zero energy ranges. The
width of each range is two times this value. All ranges are equally wide. The zero
energy range is located symmetrically around the setpoint X5. The cooling range is
located immediately above the upper limit of the zero energy range. The heating
range is located immediately below the lower limit. See the Operation diagram later
in this section.
Minimum cooling
setpoint P5 Number type: decimal, Unit: Degrees
Default: 13, Range: 5 through 27
This field is intended for use as the lowest allowable discharge air setpoint during
cooling, that is, the maximum cooling effect.
Maximum heating
setpoint P6 Number type: decimal, Unit: Degrees
Default: 35, Range:10 through 60
This field is intended for use as the highest allowable discharge air setpoint during
heating, that is, the maximum heating effect.
Minimum mixed air
setpoint P7 Number type: decimal, Unit: Degrees
Default: 13, Range: 5 through 32
Lowest mixed air, or discharge air setpoint while in the ZEB range.
ZEB/Load reset mode P8 1 = ZEB (Zero energy band)
2 = Heating control setpoint
3 = Cooling control setpoint
4 = Heating and cooling control setpoint
Room humidity limit P10 Number type: decimal, Unit: Percent
Default: 65 percent rh, Range: 40 through 80 percent rh
Heating reset range P11 Number type: decimal, Unit: Deg
Default: 15, Range: 15 through 25
Cooling reset range P12 Number type: decimal, Unit: Deg
Default: 6K, Range: 0 through 20
Mixed air reset range P13 Number type: decimal, Unit: Deg
Default: 7, Range: 0 through 25
humidity sensor type (radio button) P4 Selection of the type of the humidity sensor (relative or absolute humidity).
Range: 0 through 1, default: 1 (1= relative, 0= absolute)
humidity sensor (radio button) P9 Selection whether or not a humidity sensor is connected.
Range: 0 through 1, default: 1 (1= with sensor, 0= no sensor)
Parameter Number
Descriptions P3 Comfort range
P4 Relative (1) or absolute (0) humidity sensor
P5 Minimum cooling setpoint
P6 Maximum heating setpoint
P7 Minimum mixed air setpoint
P8 ZEB/Load reset mode:
1=ZEB
2=Heating control setpoint
3=Cooling control setpoint
4=Heating and cooling control setpoint
P9 With (1) or without (0) humidity sensor
P10 Room humidity limit
P11 Heating reset range
P12 Cooling reset range
P13 Mixed air reset range
P14 Setpoint X5, if X5 is a parameter (not for Excel Web / Excel Web II).
:

Table of Contents

Other manuals for Honeywell EXCEL 5000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell EXCEL 5000 and is the answer not in the manual?

Honeywell EXCEL 5000 Specifications

General IconGeneral
BrandHoneywell
ModelEXCEL 5000
CategoryControl Systems
LanguageEnglish

Related product manuals