EXCEL CARE CONTROL ICONS EXAMPLES
253 74-5577–33 (US)
EN2B-0184 GE51 R0518 (Europe)
In addition to floating limits, the system should suppress all alarms as long as the
supply air fan is off because the supply air sensor cannot measure correct values
when the fan is off. The following diagram illustrates both alarm suppression and
floating limits.