S3 Series UL Listing Document — P/N LS10005-051GF-E:D3 3/09/2016 57
Section 9: System Power/Size
Table 9.1 lists the System Power/Size currents.
Table 9.2 lists the System Capacity
.
Power Current
Max. AH
Capacity
Derating
Factor Max. Standby
Current
Max. Alarm
Current
Max.
Standby
Time
Max. Alarm
Duration
Max.
Charging
Current
Primary
(Power Supply)
7 A 55 A/H .2 *3.5 amps
max.
continuous
Standby
(when the
FLPS-7 is
used with the
SLP-E3).
*7 amps
Alarm max.
continuous
N/A N/A 1 amp
Secondary
(Backup)
7 A 55 A/H 1.4 amps 7 amps
max.
24 Hour 5 Minutes N/A
NOTE: * The asterisk indicates that the current is based on the Battery Calculation for 4-72
hours Standby Service.
Table 9.1 Power Supply Currents
Accessories/Sub-Assemblies/
Networked panels
Maximum System Capacity
Devices SLC-PM
(System Sensor Devices)
SLC95-PM
(Apollo Devices)
Monitor and Control Modules 318 Modules 252 Modules/Detectors
Detectors 318 Sensors
Initiating Device Circuits (SLC) 128 SLC Circuits for a Single-Ring
Network
244 SLC Circuits for a Multi-Ring
Network
128 SLC Circuits for a Single-Ring
Network
244 SLC Circuits for a Multi-Ring
Network
Table 9.2 System Capacity