MAN0905_Issue 7_07/17 Searchpoint Optima Plus with optional HART
®
output
Operating Instructions
2108M0550
52
12. Commissioning using
HART
®
Communications
Read this chapter if HART
®
communications are being used to communicate with
Searchpoint Optima Plus.
Note:TheinstructionsthatfollowassumethatasuitableHART
®
host (handheld or PC) is connected to the
SearchpointOptimaPlusandthattheuserisloggedinwithLevel1accessprivileges.SeeChapter11“Use
oftheHART
®
Communications” for details.
12.1 Introduction
This chapter explains several operations that may be required during commissioning. The user should work
throughFirstTimeSwitchOn,UserCongurationandCongureDeviceIdenticationInformation,before
selectingfurtheroperationsasrequiredbythespecicinstallation.
First Time Switch On
Checks that are required on rst power up
User Conguration
How to change settings from the default values: -
Change the Password – How to change the password for Level 1 access
Congure HART
®
Operation during Fault - How to change the Fault
output level to 1 mA so that HART
®
will operate during Fault
Set the Time and Date - How to adjust the real time clock to local time
Congure Warning, Inhibit and Overrange Signal Levels - How to
change the signal levels from the default settings
Congure Device Identication Information
How to set text elds that may be useful for device identication
Fix the 4-20 mA Output
How to force the mA output to set levels in order to calibrate the controller
or test the system
Test 4-20 mA Loop Integrity
How to check that there is sufcient compliance in the loop to signal alarm
and overrange
Calibrate the 4-20 mA Loop
How to calibrate the current output (note this is not a gas calibration)
Congure Internal Alarm Threshold
How to change the internal threshold used to simulate Alarm and log gas
events
Simulation
How to test the system by simulating Alarm, Warning and Fault conditions
Clear Faults or Warnings
How to clear faults or warnings that may be generated during
commissioning
Caution: After changing any parameter, poll the Searchpoint Optima Plus and verify that the received
value is correct.
Note:TheinstructionsthatfollowassumethatasuitableHART
®
host (handheld or PC) is connected to the
SearchpointOptimaPlusandthattheuserisloggedinwithLevel1accessprivileges.SeeChapter11“Use
oftheHART
®
Communications” for details.