Honeywell Searchpoint Optima Plus - 3.2.5 Installation of gassing pipes for Remote Gassing Cell

Honeywell Searchpoint Optima Plus
97 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MAN0905_Issue 7_07/17 Searchpoint Optima Plus with optional HART
®
output
Operating Instructions
2108M0550
24
4. Screw the unit into the junction box until the assembly is secure with the mounting plate trapped
between the box and the Searchpoint Optima Plus.
5. Remove the covers from the ends of the gassing cell inlet tubes.
6. Attach the gassing tubing to the ends of the gassing cell inlet tubes.
7. Fasten the mounting plate to the wall of the duct, ensuring that the seal is compressed.
8. Fitapprovedcableglandstothejunctionboxcableentriesasrequiredtomaintainthecertication
and IP rating.
9. Fitapprovedblankingplugstounusedjunctionboxcableentriesasrequiredtomaintainthecertication
and IP rating.
10.Fittheexternaleldwiringthroughthecableglandsandsecure.
11.TerminatethegasdetectorandeldwiringinaccordancewithChapter4(ElectricalInstallation).
3.2.5 Installation of gassing pipes for Remote Gassing Cell
Remote Gassing Cell
High Concentration
(v/v cell) Nozzles
The Remote Gassing Cell (RGC) is used for functional response checking (bump testing) when the
SearchpointOptimaPlusisinstalledinaninaccessiblelocation.TheRGCshouldbettedwithgassing
accessoriesasfollows:-
1. Useaninletpipettedwithaninlineparticlelter.
2. Useanexhaustpipettedwithaone-wayvalve.
3. Ensure that the exhaust vents well away from the Searchpoint Optima Plus to avoid affecting the gas
reading.
4. HighconcentrationgaswillbeusedintheRGC.Ensurethattheexhaustventssafely.