95
23. Appendix 5 –
HART
®
Commands Used
23.1 Universal Commands
SearchpointOptimaPlusrespondstotheUniversalCommands.OneDynamicVariableisimplemented–
Gas Concentration.
Additionalcomments:-
• Command #3 returns loop current and PV.
• Command#14:Unitsforsensorlimitsandminimumspanarexed.Sensorserialnumberisnotused,
and returns 0
• Command#38:Reset“CongurationChanged”Flag
• Command#48:ReadAdditionalDeviceStatus
23.2 Common-Practice Commands
23.2.1 Supported Commands
Thefollowingcommon-practicecommandsareimplemented:
Command Number Description
40 Enter/Exit Fixed Current Mode
41 Perform Device Self-Test
42 Perform Master Reset
45 Trim DAC Zero
46 Trim DAC Gain
23.2.2 Burst Mode
Searchpoint Optima Plus does not support Burst Mode.
23.2.3 Catch Device Variable
Searchpoint Optima Plus does not support Catch Device Variable.