EasyManua.ls Logo

Honeywell Searchpoint Optima Plus - 14.2 WARNING and FAULT messages; 14.3 Further Assistance

Honeywell Searchpoint Optima Plus
97 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MAN0905_Issue 7_07/17 Searchpoint Optima Plus with optional HART
®
output
Operating Instructions
2108M0550
73
W / F – Obscured
Optics (error 8)
Warning / Fault
Obscured optics
Contamination in the optical
path.
1. Remove the weather protection and dust
barrier. Replace the dust barrier if required.
2. Clean optics and carry out a Soft Reset (see
Maintenance, Inspection).
F – Signal Quality
(error 16)
Fault
Poor signal quality
Optical signal is low, noisy or
unstable
1. Remove the weather protection and dust
barrier. Replace the dust barrier if required.
2. Clean optics and carry out a Soft Reset (see
Maintenance, Inspection).
W / F– Lamp Output
(error 11)
Warning / Fault
Lamp output
Lamp signal is low. 1. Clean optics and carry out a Soft Reset (see
Maintenance, Inspection).
2. If the Fault / Warning does not clear, return unit
for repair.
W / F – Internal Failure
(error 22)
Note:thiserrorwill
LATCHthe4-20
mA output
Warning / Fault
Hardware failure
Note:thiserror
willLATCH
the 4-20 mA
output
Internal hardware fault 1. Cycle the power or carry out a Reset to restart
the unit. See Maintenance, View and Clear Faults
or Warnings
2. If the fault persists return the unit for repair.
F - Hardware Fault
(error 13)
Fault
Hardware Fault
The latched faults or
warnings ag has been set
1. This error may occur following Self Test.
2. Check for any active Faults or Warnings.
3. If none present, cycle the power or carry out a
Reset to restart the unit. See Maintenance, View
and Clear Faults or Warnings.
4. Repeat Self Test to conrm that the Fault has
cleared.
5. If the Fault does not clear, return unit for repair.
14.3 Further Assistance
Iftheproblemisstillunresolved,pleasecontactHoneywellAnalyticstechnicalsupportusingthecontact
details on the back page of this manual.
Pleasehavethefollowinginformationtohand:-
A description of the problem, including the steps taken to try to resolve it
The serial number of the Searchpoint Optima Plus
ForSearchpointOptimaPlusunitswithHART
®
, please also locate the following information by selecting
DeviceInfofromtheDeviceSetupmenu:-
• Devid(uniqueSearchpointOptimaPlusidenticationnumber)
• Flddevrev(revisionnumberoftheHART
®
DDle)
Software rev (Searchpoint Optima Plus software revision number)
• Hardwarerev(SearchpointOptimaPlushardwarerevisionnumber)
14. Problem Solving

Table of Contents

Other manuals for Honeywell Searchpoint Optima Plus

Related product manuals