1. Select Device Setup.
2. Select Assembly Details.
3. Select Description.
4. Enter required information up to 26 characters (for example the device type) and press Enter.
5. Select Assembly Date.
6. Enterrequiredinformationintheformatmm/dd/yy(forexamplethedateofinstallation)andpressEnter.
7. Select Assembly Number.
8. Enterrequiredinformationupto8characters(forexampleanumberrelatedtotheinstallation)and
press Enter.
9. Select Device Tag.
10.Enterrequiredinformationupto8characters(forexampleauniquedeviceidenticationnumber)
and press Enter.
11. Select Transmitter ID.
12. Enter required information up to 32 characters (for example the device location) and press Enter.
13. Press Send to send the information to Searchpoint Optima Plus.
14. Return to the Welcome screen.
12.5 Fix the 4-20 mA Output
The4-20mAoutputcanbesettoaxedvaluebetween1mAand21mA,whichcanbeusedtocalibrate
the controller, or to test the system.
Note:Thisfunctionwilltimeoutafter10minutesofinactivity.
Note:Whenconnectingordisconnectingamultimeter,powerofftheSearchpointOptimaPlus,otherwise
the unit will indicate a latched warning that the 4-20 mA loop was broken. If this occurs, it can be cleared
usingtheHART
®
communications. See Clear Faults or Warnings.
1. Select Device Setup.
2. Select Test
3. Select mA Loop Test
4. The display shows a warning message, press OK.
5. Select required analogue output level and press Enter.
Searchpoint Optima Plus will now output the set mA value.
6. When ready, press OK
7. Repeat steps 4 and 5 with another value if required, or select End.
8. ThedisplayshowsanotethattheSearchpointOptimaPluswillreturntonormaloperation,pressOK.
9. Thedisplayshowsaconrmationmessage,returntotheWelcomescreen.
12. Commissioning using
HART
®
Communications