EasyManua.ls Logo

Honeywell XLS80e - Remote Fire Output Options

Honeywell XLS80e
138 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
103 Honeywell, Issue 9
March 2007
XLS80e Fire Alarm Control Panels
11.18 Remote Fire Output Options
These options allow each of the four internal
sounder/relay circuits and the Fire VFCO Relay
to be configured in software as Remote Fire
Outputs.
1 Select the circuit or relay to be configured.
2 Select the required option for the circuit or
relay. If any of Outputs 1 to 4 are set to
Sounder/Relay, then the Sounder or Relay
function is selected by a hardware link as
described in the XLS80e Series Installation
and Commissioning Manual.
Note: After a circuit has been configured as a
Remote Fire Output it is no longer
subject to any configured sounder
delays. The Day Mode function
(Section 11.19) sets delays for Remote
Fire Outputs.
Network systems only - if none of the outputs
are set to Remote Fire Outputs, select YES if
the Remote Fire Output is on a remote panel.
This then allows you to configure Day/Night
Modes on the local panel.
Systems on which at least one Virtual Output
Point has been configured and assigned to a
zone - press from the menu of step 1 above
to display the Virtual Output Backup Sounder
option (see Section 15.3).
(AT CONFIRM
PROMPT)
FIRE OUTPUT SETTINGS TAKE EFFECT
IF OPTION 5 IS SELECTED:
IF OPTION 1, 2, 3 OR 4 IS SELECTED:
Virtual Point Configuration
Select Sounder Circuit to be Backup
for Virtual Output (1-4; 0=none): 1

Table of Contents

Related product manuals