XLS80e Fire Alarm Control Panels
Honeywell, Issue 9
March 2007
12.5 Commissioning Mode for MCS
Sensors
MCS sensors incorporate an internal delay
(approx 10 minutes) when they are set to
sensitivity level L4 or L5. The latter is the
default, thus to enable these sensors to be
commissioned a test mode can be invoked
which sets them to L3 for a defined time. This
option is only available if MCS sensors are
configured on the loops. It is accessed at
level 3 from the Test menu:
1 Select Commissioning Mode ON.
2 Enter the required time in hours.
The Test tab then displays the time remaining
until the end of Commissioning Mode, at which
all MCS sensors revert to their programmed
Alarm sensitivity level. To end Commissioning
Mode before this time, display the Test tab and
press and then confirm the cancellation.
Commissioning Mode for MCS sensors
Time remaining: 01:56:44
CANCEL Commissioning mode ( /X)?
Test Service Mon 22-Jan-2007 10:04:11
Commissioning Mode for MCS sensors
Time remaining: 01:56:44
Test Service Mon 22-Jan-2007 10:04:11
Commissioning Mode for MCS sensors
1:OFF
2:
Duration (hours: 1-12): _
Service Mon 22-Jan-2007 10:04:11
ON
Commissioning Mode for MCS sensors
1:
2:ON
Service Mon 22-Jan-2007 10:04:11
OFF
Test Menu:
1:Zone Walk Test
2:Control Output/Sounder Test
3:Lamp Test
4:
Service Mon 22-Jan-2007 10:04:11
Commissioning Mode for MCS sensors