19
XLS80e Fire Alarm Control Panels
Honeywell, Issue 9
March 2007
3.15 Delays
Either the sounders or the fire alarm routing
equipment (remote fire outputs) which is used
to summon the fire brigade can be delayed:
a. To activate sounders immediately but delay
the remote fire outputs, use the Day/Night
Modes Configuration Option
(Section 11.19). The delay may be
extended to allow investigation. MCPs are
normally configured to override any delay.
b. To delay sounders but activate the remote
fire outputs immediately, use the Control
Matrix to put an output delay on modules of
type BELL (Section 7.6.2.2). The delay
must then be enabled by the Operator (see
997-474, Operating Manual Section 7.5).
MCPs are normally configured to override
any delay.
3.16 Virtual Point Configuration
Up to 64 Virtual Input Points and up to 512
Virtual Output Points can be configured. They
are used with external systems (e.g. a Voice
Alarm panel) with which they communicate via
an RS232 port. They must be placed in a zone;
they then become possible inputs to or outputs
from the Control Matrix. Further information is
given in Section 15.