14.2.3 Associate Repeaters with Panel
When a station type is selected as Repeater,
the Repeater is associated by default with the
Master panel. To change the association:
1 Use the pushbuttons to
highlight the panel that the Repeater is
currently associated with.
2 Use numeric pushbuttons to enter the panel
number (0 for Master, 1 to 7 for Slave) with
which the Repeater is to be associated,
then press .
In this example Repeater 3 is associated with
the Slave 1 panel.
Note: If a panel is deleted or changed to a
repeater, all repeaters associated with
it have their association changed
automatically to MASTER.
The following error messages may be
displayed:
a. ‘ERROR: Station n is not a PANEL’. You
cannot associate a repeater with another
repeater, only with a panel.
b. ‘Association only applicable to
REPEATER’. You cannot associate a panel
with a repeater.
14.2.4 Completion of Network
Configuration
When all network configuration edits have
been completed for the panel, press . At
the prompt, press again to confirm the
changes.
14.3 Print Network Configuration
This option prints the configuration of the
network.
TYPICAL ERROR MESSAGE:
NUMERIC
ENTRY