61 Honeywell, Issue 9
March 2007
XLS80e Fire Alarm Control Panels
7.5 Review/Edit Control Matrix
This option allows you to examine the existing
Control Matrix entries and amend or delete
individual entries.
7.5.1 Review Entries
Use the and arrows to step through
the entries. Each entry has the format INPUT
definition OUTPUT definition. The order in
which the entries appear has no significance.
The # number is a delay number, for reference
only.
If there are several delayed actions sharing
the same delay, they are shown as separate
entries. In this example two entries with
different inputs and the same output use the
same delay but with different periods.
It is also possible for two entries with the same
input but different outputs to share a delay, but
the periods must be the same.
If a Control Matrix entry has a time-of-day
program configured, press to view the
time-of-day settings, and press to return
to the input and output display.
FOR EXAMPLE:
A DELAY MAY BE SHARED:
A TIME-OF-DAY PROGRAM MAY EXIST:
Control Matrix Configuration 5
INPUT:
Control Matrix input definition
OUTPUT:
Control Matrix output definition
=edit/delete *=new entry X=cancel
Control Matrix Configuration 18
INPUT:
ZONE 3 (Coincidence)
OUTPUT: (Sounder Delay #1 48s)
ZONE 4, BELL (Pulsed)
=edit/delete *=new entry X=cancel
Control Matrix Configuration 3
INPUT:
ZONE 5
OUTPUT: (Sounder Delay #2 64s)
ZONE 6, BELL
=edit/delete *=new entry X=cancel
Control Matrix Configuration 4
INPUT:
ZONE 6
OUTPUT: (Sounder Delay #2 80s)
ZONE 6, BELL
=edit/delete *=new entry X=cancel
Control Matrix Configuration 11
INPUT:
ANY ZONE
OUTPUT: (Time-of-day dependent)
Internal SOUNDER Cct.3
=edit/delete *=new entry X=cancel
Control Matrix Configuration 11
(Time-of-day dependent)
Not effective at following times:
-MTWTF- 0830-1730 0000-0000
S-----S 0000-0000 0000-0000
=edit/delete *=new entry X=cancel
Control Matrix Configuration 9
INPUT:ALARM:
Virtual Input Point 8
OUTPUT:(Sounder Delay 40s)
Virtual Output Point 512
=edit/delete *=new entry X=cancel
INPUTS AND/OR OUTPUTS MAY BE VIRTUAL: