XLS80e Fire Alarm Control Panels
Honeywell, Issue 9
March 2007
5.1.2 Change Device Configuration -
Sensors
The following can be altered for sensors:
a. The device type.
b. The zone or cell in which the device is
placed.
c. The device location text. Note that the zone
text is displayed but cannot be edited here
(it is edited in the Zone Text Editor, see
Section 6.3).
d. Sensitivity levels (see Section 13 for
recommendations).
e. Verification delay times. See Section 13 for
recommendations.
f. Priority option.
g. Time-of-day sensitivity changes.
5.1.2.1 Edit Device Type
Select the required TYPE. If no sensor exists
at the entered number, its type is NONE.
Available types are:
Type Description Physical Type
NONE Deleted - no sensor
exists at this address
HEAT Thermal sensor TC808
ION IONisation sensor TC807
OPT Photo sensor TC806
MULT Photo/Thermal sensor TC840
LASR Photo ‘Laser’ sensor TC846
GAS Gas Sensor Interface
MCS4 Optical/thermal/infra-red/
carbon monoxide
If you change a device type, the other settings
(except zone, cell and device text) revert to
default.
Gas Sensor Interface
Interface IIG1 requires three consecutive
sensor addresses; the lowest is shown as type
GAS and the other two as NONE. Interface IIG4
requires up to twelve consecutive addresses
(depending upon how many of four possible
interfaces are configured at the device), the first,
fourth, seventh and tenth are type GAS and the
others NONE. The following then applies:
i Attempts to change the type at the
addresses shown as ‘NONE’ display the
message ‘This address is not available:
GAS sensor occupying one of the previous
two addresses.’.
ii Type GAS cannot be configured at an
address if either or both of the next two
addresses are already occupied (the
message ‘PLEASE DELETE next two
higher-addressed sensors before installing
GAS sensor at this address.’ is displayed).
TO
MAKE
SELECTION
GAS SENSOR INTERFACE:
This device produces a Technical
Alarm by default, but can be
configured as a Fire Alarm by the
configuration option shown below. The Control
Matrix groups Technical Alarms with Fire Alarms.
Device Configuration - Loop 3 Sensor 8
Type GAS Zone 203 Cell 0
Zone <Storage area >
Loc. <First IIG4 >
=select *=edit =next device =finish
TECHNICAL ALARM device:
Device Configuration - Loop 3 Sensor 8
1:Normal Alarm Input
2:TECHNICAL ALARM device
Set device type - Loop n Sensor nn
6:OPTICAL 'LASER' SENSOR (TC846)
7:GAS Sensor Inteface (IIG1/IIG4)
8: (MCS4)
4:PHOTO (OPT) SENSOR (TC806)
5:PHOTO/THERMAL (MULT) SENSOR (TC840)
Multi Criteria 4 Sensor

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell XLS80e and is the answer not in the manual?

Honeywell XLS80e Specifications

General IconGeneral
BrandHoneywell
ModelXLS80e
CategoryControl Systems
LanguageEnglish

Related product manuals