XLS80e Fire Alarm Control Panels
7.3 Output Categories
Possible output devices or categories in a
Control Matrix entry are shown below.
SPECIFIED
DEVICE
EXTINGUISHING
ACTIVATE
OUTPUTS
Restricted-
by-type (b)
CELL
ZONE
Select
Zone(s) (a)
Select
Cell(s)
A
B
D
Select
Circuit
Select
Module
CONTROL MATRIX OUTPUTS
Select
Zone
Select
Select
Flag
TRANSFER
FLAG
ALL
OUTPUTS
SOUNDER/
RELAY
CIRCUIT
Steady/Pulsing
(NOT applicable if
input is DISABLEMENT,
RESET*, SILENCE* or
MCP in walk test*)
Delay
(NOT applicable if input
is DISABLEMENT, RESET,
SILENCE or MCP in walk test.
EXTINGUISHING:
see note [c])
TIME OF DAY
Select
END OF ENTRY
All times
(not applicable if
input is TRUE)
All times
Logic
Output (f)
No
Logic
Select
System
Select
Alarm
Operation
Soak
(if applicable
to selected
Alarm
Operation)
SPECIFIED
DEVICE
EXTING-
UISHING
ACTIVATE OUTPUTS
Restricted-
by-type (b)
CELL
ZONE
Select
Zone(s)
(a)
Select
Cell(s)
C
Select
Circuit
Select
Module
Select
Zone
DISABLE ACTIONS
ALL
OUTPUTS
SOUNDER/
RELAY
CIRCUIT
Steady/Pulsing
TIME OF DAY
Select
END OF ENTRY
Select
System
Select
Non-Alarm
Operation
Timer adjust
(available for
some
Non-Alarm
Operations
only)
Select
Flag
OTHER
Logic
Output (f)
No
Logic
SPECIFIED
DEVICE
ZONE(S)
(d)
SOUNDER/
RELAY
CIRCUIT
Sensor/
Module
Select
Zone
Select
Zone
Select
Device
Select
Circuit
Select
Zone(s)
MUTE
BUZZER
SILENCE
SOUNDERS
SYSTEM
RESET
TRANSFER
FLAG (f)
INPUT:
ALARM
(including Thermal-only Alarm)
INPUT:
PRE-ALARM
FAULT
DISABLEMENT
EVACUATE
TRANSFER FLAG
INPUT:
EXTINGUISHING
RESET
SILENCE
MCP in walk test
INPUT:
NON-FIRE
(a) IfANY ZONE is selected, the internal sounder circuits are included.
(b) Sounders 3 & 4 can be configured as volt-free relays, but are referred to as Sounders in the control matrix.
Selecting ALL OUTPUT MODULES will drive sounders 1-4, even if 3 or 4 are set as relays. ALL SOUNDER
OUTPUTS will drive sounders 1 and 2, and 3 and 4 only if they are configured as sounders. ALL CONTROL
OUTPUTS will drive sounders 3 and 4 only if they are configured as relays.
(c) If the is ALARM and the is EXTINGUISHING, and depending upon which alarm operation is
selected, a special 'activation delay' range is provided.
(d) The 'Disablement from a remote panel or switch' option in the Panel Settings 'Disablement Options' menu
determines what is disabled in the zone (sensors only, all inputs [default] or all inputs and outputs).
(e) Available only if at least one Multi-criteria sensor has been configured for 'Thermal Mode by Zone'.
(f) TRANSFER FLAG also available when input is TRUE. 'Logic Output' available only if the input is ALARM,
PRE-ALARM, NON-FIRE, another TRANSFER FLAG or TRUE.
(g) Action occurs only when input is switched from open to closed.
input output
Note: The output zone does not have to be the same as the input zone.
E
INPUT:
TRUE
* = single
pulse
SET
TO
THERMAL-
ONLY
MODE (e)
Select
Zone(s)
NIGHT
MODE (g)
DAY
MODE (g)
EXTEND
DELAY (g)
OVER-RIDE
DELAY (g)
VIRTUAL
OUTPUT
POINT
Select
Point
Mode
1or2
VIRTUAL
OUTPUT
POINT
Select
Point
Mode
1or2
VIRTUAL
OUTPUT
POINT
Select
Point