XLS80e Fire Alarm Control Panels
Honeywell, Issue 9
March 2007
5.3.3 Run in Manual Learn Mode
If you select this option, then:
1 Press to begin the manual learn
process.
2 As the learn process progresses, the status
is displayed.
3 If a difference is found, the process halts
and a menu is displayed (the menu
depends upon the format; two examples
are shown left). If you are asked for a device
type, then after you have made your
selection you will be prompted for a zone
number.
5.3.4 Error Messages
Example messages are shown opposite. The
learn process always halts when an error
(other than ‘unterminated module’) occurs.
This indicates a general communication fault
or inconsistent results from successive scans.
It may be due to a faulty device, or an
incorrectly-installed loop.
This indicates that a sensor with the wrong
protocol has been installed.
This indicates that two or more devices have
been set to the same address.
This indicates that the Loop Interface Board
(LIB) has stopped responding. If this occurs
repeatedly, the panel should be examined by
a service engineer.
Additional message (not an error) - if many
devices have been learnt, the panel may run
out of temporary buffer memory. Press .
The panel then continues its learn process.
REFER TO SECTION 5.3.5 FOR DETAILS OF
THE END OF THE LEARN PROCESS
EXAMPLE MENUS THAT MAY BE DISPLAYED: