67 Honeywell, Issue 9
March 2007
XLS80e Fire Alarm Control Panels
IF OPTION 4 (DISABLEMENT) IS CHOSEN:
IF OPTION 3 (FAULT) IS CHOSEN:
IF OPTION 2 (PRE-ALARM) IS CHOSEN:
IF OPTION 5 (NON-FIRE ACTIVATION) IS CHOSEN:
7.6.1.2 PRE-ALARM
To define the PRE-ALARM input, select
option 2 from the Configuration Menu. Follow
the procedure as for ALARM. The ‘Zone’ and
‘greater than 2 devices’ in coincidence options
are not available for PRE-ALARM.
7.6.1.3 FAULT
ZONE
Select a zone. ANY Zone includes PSU, panel and
system faults that are not attributable to a zone.
General Panel Fault
Selects any fault as the input.
Virtual Input Point
Future development.
7.6.1.4 DISABLEMENT
Select ZONE or one of the other disablement
options from the menu.
ZONE
Select a specified panel, or any panel, as the
input. No further input options are displayed.
General Panel Disablement
Select the required output option.
Note: A general output panel disablement is
defined as ANY input OR output that
causes the DISABLEMENT LED to light.
Sounders Disabled
Select which sounder outputs are to be
disabled.
Remote Fire Output Disabled
Select the required output module/relay option.
Virtual Input Point
Future development.
7.6.1.5 NON-FIRE ACTIVATION
Follow procedure as for ALARM or
PRE-ALARM. The input must be of type AUX.
Zone and Device coincidence options are not
available. This option also allows panel input
1 or 2 to be selected as the input (on XLSNET
only, the panel number can be selected).
Create New Control Matrix Entry
Define Matrix INPUT: Please select:-
PRE-ALARM
1:
2:Specified Individual Device
3:Virtual Input Point
Cell, Zone or Panel
Create New Control Matrix Entry
Define Matrix INPUT: Please select:-
NON-FIRE ACTIVATION
1:
2:Specified Individual Device
3:Virtual Input Point
Cell, Zone or Panel
Create New Control Matrix Entry
Define Matrix INPUT: Please select:-
NON-FIRE ACTIVATION
3:Virtual Input Point
4:Panel Input 1
5:Panel Input 2