Menu Parameter Description Setting Guide
Liquid pipe
length
Set this parameter
based on the actual
length of the liquid
pipe.
-
Height
dierence
between
indoor and
outdoor units
Set this parameter
based on the actual
height dierence
between indoor and
outdoor units.
-
Heating
function
If this parameter is set
to Enable, the device
starts heating when
the ambient
temperature is lower
than the temperature
setpoint by a certain
range. If this
parameter is set to
Disable, the heating
function is disabled. If
this parameter is set to
Enabled when active
power, the device
starts heating only
when the primary
power is used and the
ambient temperature is
lower than the
temperature setpoint
by a certain range.
Retain the default
value.
Heating mode This parameter can be
set to Dehumidifying
heating, Low-
temperature heating,
or Dehumidication &
Low temperature
heating.
Retain the default
value.
NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual 6 Power-On Commissioning
Issue 08 (2021-09-17) Copyright © Huawei Technologies Co., Ltd. 132