Menu Parameter Description Setting Guide
Temperature
setpoint
After the temperature
and humidity control
type and the
temperature value
under this type are set,
the device performs
cooling or heating
based on the settings.
Set this parameter
as required.
Return air
temperature: 26–
35°C
recommended
Supply air
temperature: 18–
24°C
recommended
Cold aisle
temperature: 18–
24°C
recommended
Hot aisle
temperature: 26–
35°C
recommended
Humidity
setpoint
After the temperature
and humidity control
type and the humidity
value under this type
are set, the device
performs humidifying
or dehumidifying
based on the settings.
Set this parameter
as required.40%–
60% RH
recommended
Settings >
Quick Settings
> Comm
Settings
Modbus
Comm
address
Enter the
communications
address of the smart
cooling product as
planned. The NMS
communicates with the
smart cooling product
using this address, and
the communications
addresses of two smart
cooling products
connected to the same
NMS must be
dierent.
Set this parameter
based on NMS
planning.
----End
Follow-up Procedure
After powering on, the compressor starts preheating, and the system generates an
alarm indicating that the compressor is preheating (for 12 hours). Do not start the
NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual 6 Power-On Commissioning
Issue 08 (2021-09-17) Copyright © Huawei Technologies Co., Ltd. 136