NO TE
If the DHCP server is congured on the NMS, select Auto (DHCP). If no, set this parameter
to Manual.
Step 2 On the home screen, choose Settings > Comm Settings > Modbus Settings and
set Link mode to Server and client or Client. Set Client encryption to Enable.
Figure 6-17 Modbus Settings 1
Figure 6-18 Modbus Settings 2
Step 3 Enter the actual IP address of the NMS.
Step 4 When Client encryption is set to Enable, set NMS port number to 32907. When
Client encryption is set to Disable, set NMS port number to 32906.
NO TE
The encryption mode must be the same as it on the NMS.
NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual 6 Power-On Commissioning
Issue 08 (2021-09-17) Copyright © Huawei Technologies Co., Ltd. 152