EasyManua.ls Logo

IDEAL HP290 - Table 23 Discharge Pressure (P1) for Heating;Dhw Mode

IDEAL HP290
160 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Section 9 - Fault Finding
107
Installation and Maintenance
FAULT FINDING
9.1.29 Low Pressure Sensor Error
9.1.30 High Pressure Sensor and Low Pressure Sensor Wiring-Cross-Connection
Is the cable from the Outdoor PCB to the Low Pressure
Sensor undamaged and dry?
Refer to Figure 67 on page 116.
Are the wiring assemblies to the High Pressure sensor
and Low Pressure sensor installed correctly?
Refer to Figure 67 on page 116.
Disconnect the Low Pressure Sensor. Is the displayed
voltage between 0.5 V DC and 4.5 V DC?
Replace the Outdoor PCB.
Replace the Outdoor PCB.
The wiring assembly must be undamaged,
the connections must be dry, and the
wiring assembly must be correctly
connected to the Low Pressure Sensor.
Refer to the applicable wiring diagrams.
Make sure that the wiring assemblies are
installed correctly.
Replace Low Pressure Sensor.
NO
NO
NO
YES
YES
YES
Remove the Discharge Thermistor (Tp) from the

the thermistor reading is correct. Refer to the values
shown below:




Are the Outdoor Unit Flow thermistor and the Return
thermistor installed correctly?
Is the P1 comp. pressure correct? Refer to Table 23 -
Discharge pressure (P1 for heating / DHW mode).
Replace the Outdoor PCB.
Replace Discharge Thermistor.
Install the Flow Thermistor and the Return
Thermistor.
Repressurise the refrigerant.
NO
NO
NO
YES
YES
YES
Unit Value

25 30 35 40 45 50
P1 (kPa)
1000 ±100 1150 ±100 1300 ±100 1450 ±100 1600 ±100 1800 ±100

55 60 65 70 75
P1 (kPa)
2000 ±150 2200 ±150 2450 ±150 2700 ±150 3000 ±150
Note: P1 is absolute pressure.
Table 23 Discharge pressure (P1) for heating/DHW mode
9.1.28 Compressor Discharge Temperature High Error

Table of Contents

Related product manuals