PRODUCT INFO
9
Installation and Servicing
Section 2 - Product Information
Table 1 Data - Heat Pump Outdoor Unit
Description Unit HP290 4.5 kW HP290 6 kW HP290 8 kW HP290 10 kW HP290 12 kW HP290 14 kW
Physical Properties
Packaged Weight - Gross (Unpackaged
Weight (Net))
kg 110 (90) 110 (90) 139 (117) 157 (135) 157 (135) 157 (135)
Height (Unpackaged) mm 717 717 865 865 865 865
Width (Unpackaged) mm 1299 1299 1385 1385 1385 1385
Depth (Unpackaged) mm 426 426 523 523 523 523
Performance Data
Coefficient of Performance (A+7 at W35) COP 5.15 4.9 4.7 4.8 4.5 4.4
Coefficient of Performance (A-7 / W55) COP 3.2 3.1 3.05 3.1 3 2.85
Coefficient of Performance (A+7 / W35) COP 3.1 2.95 2.85 2.8 2.7 2.5
Coefficient of Performance (A-7 at W55) COP 2.2 2.15 2.1 2.15 2.1 2.05
Seasonal Coefficient of Performance (W35 /
W55)
SCOP (5.07 / 3.79) (4.89 / 3.82) (5.07 / 3.82) (4.67 / 3.62) (4.63 / 3.61) (4.59 / 3.57)
Sound Power Level * dB (A) 56 58 61 65 65 69
Sound Pressure Level @ 1m dB (A) 44 46 49 51 52 56
Maximum Outdoor Temperature °C 46 46 46 46 46 46
Minimum Outdoor Temperature °C -25 -25 -25 -25 -25 -25
Heat Output
A+7°C/W+35°C kW 4.5 6.2 10.0 12.0 14.0 15
A+7°C/W+55°C kW 4.6 6.2 9.5 12.0 14.0 15.0
A-7°C/W+35°C
kW 4.5 5.9 8 10 11.5 12.7
A-7°C/W+55°C kW 4.7 5.2 7.4 10.4 11.3 12.4
Electrical Properties
Electrical Supply Requirements
Rated Supply Voltage V 220 ~ 240 220 ~ 240 220 ~ 240 220 ~ 240 220 ~ 240 220 ~ 240
Frequency Hz 50 50 50 50 50 50
No. of Supply Phases - 1 1 1 1 1 1
Maximum Current A 12 13.5 17.5 25 26.5 28
Fuse Rating A 20 20 25 32 32 32
Outdoor Unit Properties
IP Rating - IP24 IP24 IP24 IP24 IP24 IP24
Compressor Control Type - Inverter Inverter Inverter Inverter Inverter Inverter
Electrical Power Consumption
A+7°C/W+35°C kW 0.874 1.265 2.128 2.5 3.111 3.409
A+7°C/W+55°C kW 1.438 2 3.115 3.871 4.667 5.263
A-7°C/W+35°C kW 1.452 2.419 2.807 3.571 4.259 5.08
A-7°C/W+55°C kW 2.136 3.524 3.524 4.837 5.38 6.049
Heating Circuit Requirements
Hydronic Connections “ G 1” BSP G 1” BSP G 1 1/4” BSP G 1 1/4” BSP G 1 1/4” BSP G 1 1/4” BSP
Maximum Operating Pressure bar 3 3 3 3 3 3
Minimum Flow Rate of the Hydronic Circuit l/min 6.67 6.67 6.67 11.67 11.67 11.67
Maximum Flow Temperature °C
75 75 75 75 75 75
Minimum Operating Water Temperature
(without pre-heating)
°C 12 12 12 12 12 12
Hydraulic Resistance -
Refer to Pump
Curve
Refer to Pump
Curve
Refer to Pump
Curve
Refer to Pump
Curve
Refer to Pump
Curve
Refer to Pump
Curve
Refrigerant Data
Refrigerant - R290 R290 R290 R290 R290 R290
Factory Refrigerant Charge grams 700 700 1100 1250 1,250 1,250
GWP Rating - 3 3 3 3 3 3
ODL Rating - 0 0 0 0 0 0
Flammability Rating - A3 A3 A3 A3 A3 A3
Maximum Circuit Pressure bar 35 35 35 35 35 35
Compressor Type - Twin Rotary Twin Rotary Twin Rotary Twin Rotary Twin Rotary Twin Rotary
Compressor Oil - XS-601C1 XS-601C1 XS-601C1 XS-601C1 XS-601C1 XS-601C1
* Tested in accordance with EN 12102-1 Annex A
2.1 ERP DATA
IMPORTANT: The following performance data is only applicable to brand new products.
is provided with the HP290 Heat Pump. If a HP290 Cylinder product is installed, refer to Table 5 to Table 7 within this
2.2 HEAT PUMP OUTDOOR UNIT