Section 5 - Commissioning
COMMISSIONING
76 Installation and Maintenance
5.8.9.14 For serviceman, cascade setting
Scoll through the settings with the and touch-buttons
until the correct parameter is illuminated.
Press O. Then use the
and touch-buttons.
PER_START
5minutes
10%
TIME_ADJUST
Cascade setting
PER_START sets the maximum output of the appliances, as
a % of maximum output, at start up for cascade operation.
(default: 10 %)
TIME_ADJUST sets the time period at which additional
appliances are added to, or removed from, the cascade.
(default 5 minutes)
5.8.9.15 For serviceman, HMI address setting
Scoll through the settings with the and touch-buttons
until the correct parameter is illuminated.
Press O. Then use the
and touch-buttons.
1
1
HMI address for BMS
Stop BIT
HMI address setting
5.8.9.16 For serviceman, Common setting
Scoll through the settings with the and buttons until the
correct parameter is illuminated.
Push O. Then use the
and buttons.
t_DELAY PUMP
24hours
60seconds
24hours
2.0minutes
t1_ANTILOCK PUMP
t2_ANTILOCK PUMP RUN
t1-ANTILOCK SV
Common setting
t_DELAY PUMP is the outdoor unit primary circulation pump
overrun time after the compressor switches OFF.
(default 2.0 minutes).
t1_ANTILOCK PUMP is the minimum time period necessary
until the pumps operate prevent seizing.
(default 24 hours)
t2_ANTILOCK PUMP RUN is the time period that the
pumps will operate for if they have not been operated for 24
hours (to prevent seizing)
(default 60s)
t1-ANTILOCK SV is the minimum time period necessary
before the 3-way valve will operate if it has not been cycled in
the previous 24 hour to prevent seizing.
(default 24 hours)
t2-ANTILOCK SV RUN
-2⁰C
100%
30seconds
Ta-adj.
PUMP_I SILENT OUTPUT
Common setting
Auto
Pump_O
T2-ANTILOCK SV RUN is the time period the 3-way valve
will operate for if it has been cycled in the previous 24 hours.
(default 30s)
Ta-adj. is not applicable for this appliance.
PUMP_I SILENT OUTPUT: should not be changed
(default 100 %)
Energy metering is not applicable to this product
If
Pump_O is set to ON then CH Zone 1 Pump operates
continuously.
If
Pump_O is set to Auto then CH Zone 1 Pump operates
when there is a demand in CH Zone 1.
(default 0)
Glycol - Set to Without Glycol (no function on this unit).