13
INSTALLER
USERMAINTENANCE TECHNICIAN
TECHNICAL DATA
Special provisions for appliances installed in B
23
or B
53
conguration.
Open chamber appliances type B
23
and B
53
must not be installed in rooms in which commer-
cial, cra or industrial activities are carried out where products are used that are capable of
developing vapours or volatile substances (e.g. acid vapours, glues, paints, solvents, fuels, etc.),
as well as dust (e.g. dust from wood processing, coal dust, cement dust, etc.) that could be
harmful to the appliance's components and impair its operation.
In conguration B
23
and B
53
, unless local regulations are in force, the appliances must not be
installed in bedrooms, bathrooms, toilets or studios; they must neither be installed in rooms
containing solid fuel heat generators nor in rooms communicating with said rooms.
For appliances for domestic use (up to 35 kW) in B
23
and B
53
conguration, the installation
rooms must be permanently ventilated, in compliance with the local regulations in force (at
least 6 cm
2
for each kW of heat input installed, except in the case of the presence of electrome-
chanical extractor fans or other devices that can depressurise the installation room).
Install the appliances in B
23
and B
53
conguration in non-residential premises and which are permanently ventilated.
Failure to comply with the above implies personal responsibility and invalidates the warranty.