INSTALLERUSERMAINTENANCE TECHNICIANTECHNICAL DATA
1.31 APPLIANCE STARTUP IGNITION
To commission the appliance (the operations listed below must only be performed by qualied personnel and in the presence of sta
only):
1. check that the internal system is properly sealed according to the specications set forth by regulations in force;
2. Ensure that the type of gas used corresponds to the appliance settings (the type of gas appears on the display on rst electrical power
supply);
3. check that there is no air in the gas pipe;
4. Check connection to a 230V~50Hz power mains, correct L-N polarity and the earthing connection;
5. check that the intake/exhaust terminals are not obstructed and that they are installed properly;
6. Check that the drain trap is full and that it prevents any passage of ue gas into the room;
7. check that there are no external factors that may cause the formation of fuel pockets;
8. Carry out the ue test (Par.3.12);
9. Activate the automatic calibration function (TA) (if in the previous check it was necessary to change the ue parameters): (Par.
3.10);
10. Switch the appliance on and check correct ignition;
11. Make sure that the gas ow rate and relevant pressure values comply with those given in the manual (Par.4.1);
12. ensure that the safety device intervenes in the event of gas supply failure and check the relative intervention time;
13. Check the activation of the main switch located upstream of the appliance and in the appliance.
Even if just one single safety check provides a negative result, do not commission the system.