Goodrive300-LIFT series inverter Function parameters
-68-
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P14.04
Communication
timeout fault
duration
0.0 (invalid), 0.160.0s
When the function code is set as 0.0, the
parameter is invalid.
When the function code is set as non-zero, if the
interval time between two communications
exceeds this parameter value, the system will
report "485 communication faults" (CE).
Generally, set it as invalid; set the parameter in
the continuous communication to monitor the
communication state.
0.0s
P14.05
Transmission
fault processing
0: Alarm and stop freely
1: No alarm and continue to run
2: No alarm and stop according to the stop mode
(only under the communication control)
3: No alarm and stop according to the stop mode
(under all control modes)
0
P14.06
Communication
processing
0x000x11
LED ones:
0: Write with response: the inverter will respond
to all reading and writing commands of the
upper monitor.
1: Write without response: the inverter only
responds to the reading command other than
the writing command of the drive. The
communication efficiency can be increased by
this method.
LED tens:
0: Communication encrypting invalid
1: Communication encrypting valid
0x00
P14.07
CAN
communication
address
0127 (0 is a broadcast address, indicating that
messages are sent but not replied)
2