Goodrive300-LIFT series inverter Function parameters
-37-
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P00.09
Motor parameter
autotuning
0: No operation
1: Rotating parameter autotuning on empty-load
asynchronous motor
2: Static parameter autotuning on asynchronous
motor
3: Rotating parameter autotuning on empty-load
synchronous motor
4: Static parameter autotuning on synchronous
motor
5: Rotating parameter autotuning on
synchronous motor with load
0
P00.10
Function
restore
parameter
0: No operation
1: Restore the default value
2: Delete the fault records
3: Roll back function parameters, reading
function parameters that are saved when the
LSB of P07.01 is set to 5.
0
P00.11
AVR function
0: Invalid
1: Valid
1
P00.12
Reserved
0-65535
0
P00.13
Reserved
0-65535
0
P01 Group Startup and stop control
P01.00
Start mode
0: Start-up directly: start from the starting
frequency P01.01
1: Start-up after DC braking: start the motor from
the starting frequency after DC braking (setting
P01.04 and P01.05)
It is suitable in the cases where reverse rotation
may occur to the low inertia load during starting.
0
P01.01
Starting
frequency of
direct start
Starting frequency of direct start-up means the
original frequency during the inverter starting.
See P01.03 for detailed information.
Setting range: 0.0050.00Hz
0.00Hz
P01.02
ACC time of start
0.0000.100s
0.010s