Communication
106 USER MANUAL FPC 200 - 3/2017
8.3.1 Miscellaneous
Measurands are transmitted with ASDU 3 as well with ASDU 9. As defined in 7,2,6,8, the maximum MVAL can
either be 1,2 or 2,4 times the rated value. No different rating shall be used in ASDU 3 and ASDU 9, i.e. for each
measurand there is only one choice.
Measurand
Max. MVAL = rated value times
1,2
or
2,4
Current L
1
X
Current L
2
X
Current L
3
X
Voltage L
1-E
X
Voltage L
2-E
X
Voltage L
3-E
X
Active power P
X
Reactive power Q
X
Frequency f
X
Voltage L
1
- L
2
X